You cannot select more than 25 topics Topics must start with a letter or number, can include dashes ('-') and can be up to 35 characters long.
lj_plc/Actions/ChemicalWeighing/Mesnac.Action.ChemicalWeighing/FinishBatch/SaveHelper/AlarmSaveHelper.cs

118 lines
5.2 KiB
C#

This file contains ambiguous Unicode characters!

This file contains ambiguous Unicode characters that may be confused with others in your current locale. If your use case is intentional and legitimate, you can safely ignore this warning. Use the Escape button to highlight these characters.

using System;
using System.Collections.Generic;
using System.Linq;
using System.Text;
namespace Mesnac.Action.ChemicalWeighing.FinishBatch.SaveHelper
{
public class AlarmSaveHelper
{
/// <summary>
/// 报警保存事件定义
/// </summary>
public static event EventHandler OnAlarmSave;
public static event EventHandler OnAlarmSaveExtend;
public static object sender = null;
public static object senderExtend = null;
private static int WordLength = 16; //定义字长
/// <summary>
/// 保存报警信息
/// </summary>
public static void Save()
{
List<Entity.AlarmInfo> _alarmInfoList = Cache.CacheHelper.AlarmInfoList;
List<Entity.SimpleAlarmInfo> _alarmBlockWordList = Cache.CacheHelper.BlockWordList;
#region 读取PLC的报警数据
foreach (Entity.AlarmInfo info in _alarmInfoList)
{
Int16[] buff = null;
if (BasePlcHelper.Instance.PlcRead(info.AlarmPLC, info.AlarmBlock, info.Start, info.Length, out buff))
{
foreach(Entity.SimpleAlarmInfo sai in _alarmBlockWordList)
{
if (sai.AlramPLC == info.AlarmPLC && sai.AlarmBlock == info.AlarmBlock) //匹配数据块
{
sai.AlarmData = buff[sai.AlarmAddress - info.Start]; //对起始字偏移,为当前字的报警值
sai.AlarmData = Mesnac.Basic.DataProcessor.Swap(sai.AlarmData); //注意西门子PLC需要高低位转换
}
}
}
else
{
ICSharpCode.Core.LoggingService<AlarmSaveHelper>.Warn(String.Format("从PLC读取报警数据失败:PLC={0},Block={1},Start={2},Len={3}", info.AlarmPLC, info.AlarmBlock, info.Start, info.Length));
}
}
#endregion
#region 保存报警数据
foreach(Entity.SimpleAlarmInfo sai in _alarmBlockWordList)
{
int[] binaryAlarmData = Mesnac.Basic.DataProcessor.ParseBinaryValue(sai.AlarmData, WordLength);
for (int i = 0; i < WordLength; i++)
{
if (sai.IsSaveAlarm[i] == true && binaryAlarmData[i] == 0)
{
//更新报警状态
Entity.PmtAlarmInfo alarmInfo = Cache.CacheHelper.GetPmtAlarmInfoFromCache(sai.AlramPLC, sai.AlarmBlock, sai.AlarmAddress, i);
if (alarmInfo != null)
{
Alarm.AlarmHelper.UpdateAlarmLogData(alarmInfo.Alarm_ID,DateTime.Now.ToString());
//清除显示的报警列表信息
if(Global.PublicVar.Instance.AlarmStrList.Exists(x => x == alarmInfo.AlarmName))
{
Global.PublicVar.Instance.AlarmStrList.Remove(alarmInfo.AlarmName);
Global.PublicVar.Instance.isFlashFlag = true;
Global.PublicVar.Instance.isFlashFlagExtend = true;
}
}
}
if (binaryAlarmData[i] == 0)
{
sai.IsSaveAlarm[i] = false;
}
if (sai.IsSaveAlarm[i] == false && binaryAlarmData[i] == 1)
{
sai.IsSaveAlarm[i] = true;
//数据保存
Entity.PmtAlarmInfo alarmInfo = Cache.CacheHelper.GetPmtAlarmInfoFromCache(sai.AlramPLC, sai.AlarmBlock, sai.AlarmAddress, i);
if (alarmInfo != null)
{
Entity.LR_Alarmlog alarmLogData = new Entity.LR_Alarmlog();
alarmLogData.Equip_Code = alarmInfo.Equip_Code;
alarmLogData.Alarm_ID = alarmInfo.Alarm_ID;
alarmLogData.Alarm_OccurTime = DateTime.Now.ToString();
alarmLogData.Alarm_ClearTime = String.Empty;
alarmLogData.Alarm_Status = 1;
alarmLogData.Alarm_GUID = Guid.NewGuid().ToString().ToUpper();
Alarm.AlarmHelper.InsertAlarmLogData(alarmLogData);
Global.PublicVar.Instance.AlarmStrList.Add(alarmInfo.AlarmName);
Global.PublicVar.Instance.isFlashFlag = true;
Global.PublicVar.Instance.isFlashFlagExtend = true;
}
}
}
}
#region 触发事件
if (OnAlarmSave != null && Global.PublicVar.Instance.isFlashFlag)
{
OnAlarmSave(sender, System.EventArgs.Empty);
}
if (OnAlarmSaveExtend != null && Global.PublicVar.Instance.isFlashFlagExtend)
{
OnAlarmSaveExtend(senderExtend, System.EventArgs.Empty);
}
#endregion
#endregion
}
}
}